Air break switch IACM 24kV 200A with rod assembly 9-11m
- Brand:
- SMICO
- Standard:
- IEC 62271-103,IEC 60265
- Electrical endurance:
- 100
- Mechnanical endurance:
- 1000
- Rated Voltage:
- 24KV
- Rated current:
- 200A
- Operating temperature:
- -25....40℃
- Storage temperature:
- -25....70℃
Description
IACM load-break disconnector switches are designed for low-load breaking overhead MV
electrical lines.
Equipped with an air-break technology system combined with an isolating switch in series,
this device provides visible opening and great safety in operation.
IACM switches are suitable for overhead distribution networks up to 24 kV, and especially
those requiring a high level of insulation:
• No maintenance required.
• Easy pole top mounting.
• Line works can be carried in safe conditions thanks to the visible opening and high level
of insulation.
• A manual control mechanism is available with a rod assembly and padlockable lever.
• Whip breaking system.
• The IACM switch control mechanisms are equipped with a tumbler spring system which
directly operates the mobile shaft.
The operating speed is not dependant on the operator.
• Height of the pole from 9 to 11 m.
• Synthetic Insulators designed with a central part in epoxy resin. The flexible skirts in over
molded silicone provide an important creepage distance and a good protection against
vandalism.
Features
| Electrical endurance: | 100 O/C | 
| Mechnanical endurance: | 1000 O/C | 
| Operating temperature: | -25 ... 40 °C | 
| Storage temperature: | -25 ... 70 °C | 
Technical characteristics
| CHARACTERISTICS | IACM 24KV | IACM 36KV | 
| Rated voltage(KV) | 24 | 36 | 
| Rated current (A) | 200/400 | 200/400 | 
| Breading capacity: | ||
| • Active load(A) | 31.5 | 31.5 | 
| •No-load transformer(A) | 2.5 | 2.5 | 
| •Close loop current(A) | 200/400 | 200/400 | 
| •Off-load line(A) | 10 | 10 | 
| Rated peak closing capacity(KV) | 12.5 | 12.5 | 
| Rated lightning impulse withstand voltage(KV peak) | ||
| •To earth and between poles | 125 | 170 | 
| •Across the isolating distance | 145 | 195 | 
| Rated 1min power frequency withstand 50 Hz/1 min(KV) | ||
| •To earth and between poles | 50 | 70 | 
| •Across the isolating distance | 60 | 80 | 
| Rated short-time withstand current(KA 1s) | 5 | 5 | 
| Rated peak withstand current(KA) | 12.5 | 12.5 | 
| Machanical endurance(cc) | 1000 | 1000 | 
In order to easy the logistics and the installation in difficult accessareas,IACM load-break
switches are made up of three independent pre-assembled poles and single frame.
 
                
             
                     
                    