Service insulation piercing connector MICHAUD
Connector general features:
- Insulation piercing is carried out on the main and tap conductors simultaneously in a single tightening operation.
-
- The dielectric strength in water is greater than 6kV.
-
- The tightening screw is potential free.
-
- Tightening efficiency is ensured by a shear head screw.
-
- ConnectorsK441,K442andK443arefittedwithayellowshearheadindicatorthatdisappearswhenheadissheared- off, being a clear visual confirmation of good tightening from ground level. It increases head height by 10 mm.
This connector meets the criteria of the NF C 33-020 and EN 50-483 standards.
Connector end cap:
- The connector end cap is flexible so that to feel good tap conductor insertion simply by hand.
-
- It is carrying membranes instead of grease, granting watertightness around tap conductor end on long term basis.
-
- It is glued on connector body so that to avoid eventual loss during handling, installation and environment (wind, bad
weather...).
-
- It can be equipped with a hard end cap, gripping and covering so, in case rigid cover is required.