Selection Of Wedge-type Tension Clamps For Lines Using Insulated Conductors
In densely populated, tree-filled, and polluted areas, we are increasingly using insulated wires to replace bare wires. Compared with bare wires, it has the advantages of high safety and reliability, reduced line loss, and less wire corrosion. When using insulated wires, we need to pay attention to the fact that since dead and clamp is clamped on the outer diameter of the "wire" when used, and dead clamp is not clamped on the outer diameter of the "conductor", the dead end clamp overhead line model used should be selected based on the outer diameter of the wire rather than the outer diameter of the conductor. For example, KLGYJ-150/8 steel core reinforced cross-linked polyethylene insulated overhead cable is used in power lines. It is calculated that its conductor outer diameter is 15.30mm, plus its insulation thickness of 3.4mm and conductor shielding thickness of 0.5mm, it can be known that its conductor outer diameter is 23.1 mm. According to the above table, the dead end clamp with eye hook that should be used is NLL-5. If we select the equipment wire clamp based on the conductor outer diameter of 15.30mm at this time, the selected dead end loop clamp*** cannot be used.
In addition, we need to tighten the screws evenly when installing dead end tension clamp, and require that there is no increase in wire stress at the contact surface between the wire and the original metal after installing fiber optic dead end clamp, so as to prevent the wire from being damaged by breeze vibration or other wire oscillation and ensure that the gripping force of fixed dead end clamp on the wire is not less than 95% of the wire breaking force.