Epoxy Resin Insulator Performance Testing And Evaluation Technology
Publish Time: Author: Site Editor Visit: 12
high voltage standoff insulators Measurement method
For single-element high voltage epoxy, its epoxy resin insulator resistance can only be measured when the power is off. The relevant high voltage epoxy resin regulations stipulate that a 2500V and above megohmmeter should be used. Currently, 2500V and 5000V megohmmeters are more commonly used, and there are also special instruments with higher voltages. But in fact, within 1*104MΩ, the 2500V and 5000V megohmmeters with the same accuracy and measured high voltage standoff insulation resistance under the same humidity are basically the same.